﻿<?xml version="1.0" encoding="UTF-8" standalone="yes"?>
<!--STOD for Hex STRING10-->
<RSLogix5000Content SchemaRevision="1.0" SoftwareRevision="20.05" TargetName="HexSTOD10" TargetType="AddOnInstructionDefinition" TargetRevision="1.1 " TargetLastEdited="2018-06-04T14:13:40.254Z" ContainsContext="true" Owner="Corning Incorporated, Corning Incorporated" ExportDate="Tue Mar 24 16:49:01 2020" ExportOptions="References DecoratedData Context Dependencies ForceProtectedEncoding AllProjDocTrans">
<Controller Use="Context" Name="none">
<DataTypes Use="Context">
<DataType Name="STRING10" Family="StringFamily" Class="User">
<Members>
<Member Name="LEN" DataType="DINT" Dimension="0" Radix="Decimal" Hidden="false" ExternalAccess="Read/Write"/>
<Member Name="DATA" DataType="SINT" Dimension="10" Radix="ASCII" Hidden="false" ExternalAccess="Read/Write"/>
</Members>
</DataType>
</DataTypes>
<AddOnInstructionDefinitions Use="Context">
<AddOnInstructionDefinition Use="Target" Name="HexSTOD10" Revision="1.1" Vendor="plctalk" ExecutePrescan="false" ExecutePostscan="false" ExecuteEnableInFalse="false" CreatedDate="2018-05-10T18:33:47.996Z" CreatedBy="Not Available" EditedDate="2018-06-04T14:13:40.254Z" EditedBy="NA\washburnpe"
 SoftwareRevision="v18.02">
<Description>
<![CDATA[STOD for Hex STRING10]]>
</Description>
<RevisionNote>
<![CDATA[Mimics STOD native instruction, except interprets characters as Hexadecimal digits. The Source input must be a standard STRING type and Dest output a DINT, unlike flexible I/O types with the native STOD. One extension:  if the HEX characters are preceded by "16#" then underscores among the HEX will be ignored (e.g., "16#1234_ABCD" is treated as "1234ABCD" for conversion purposes).
Direct questions, comments, or bug reports to user Mispeld at www.plctalk.net forums. ]]>
</RevisionNote>
<Parameters>
<Parameter Name="EnableIn" TagType="Base" DataType="BOOL" Usage="Input" Radix="Decimal" Required="false" Visible="false" ExternalAccess="Read Only">
<Description>
<![CDATA[Enable Input - System Defined Parameter]]>
</Description>
</Parameter>
<Parameter Name="EnableOut" TagType="Base" DataType="BOOL" Usage="Output" Radix="Decimal" Required="false" Visible="false" ExternalAccess="Read Only">
<Description>
<![CDATA[Enable Output - System Defined Parameter]]>
</Description>
</Parameter>
<Parameter Name="Source" TagType="Base" DataType="STRING10" Usage="InOut" Required="true" Visible="true" Constant="false">
<Description>
<![CDATA[String To Convert]]>
</Description>
</Parameter>
<Parameter Name="Dest" TagType="Base" DataType="DINT" Usage="Output" Radix="Decimal" Required="true" Visible="true" ExternalAccess="Read Only">
<Description>
<![CDATA[DINT for Result]]>
</Description>
<DefaultData>00 00 00 00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="DINT" Radix="Decimal" Value="0"/>
</DefaultData>
</Parameter>
<Parameter Name="DN" TagType="Base" DataType="BOOL" Usage="Output" Radix="Decimal" Required="false" Visible="true" ExternalAccess="Read Only">
<Description>
<![CDATA[Done/Success]]>
</Description>
<DefaultData>00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</Parameter>
<Parameter Name="EM" TagType="Base" DataType="BOOL" Usage="Output" Radix="Decimal" Required="false" Visible="true" ExternalAccess="Read Only">
<Description>
<![CDATA[Empty Source
Dest Unchanged]]>
</Description>
<DefaultData>00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</Parameter>
<Parameter Name="ER" TagType="Base" DataType="BOOL" Usage="Output" Radix="Decimal" Required="false" Visible="true" ExternalAccess="Read Only">
<Description>
<![CDATA[Conversion Error
Undefined Result]]>
</Description>
<DefaultData>00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</Parameter>
</Parameters>
<LocalTags>
<LocalTag Name="SrcLength" DataType="DINT" Radix="Decimal" ExternalAccess="None">
<DefaultData>00 00 00 00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="DINT" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="SrcIndex" DataType="DINT" Radix="Decimal" ExternalAccess="None">
<DefaultData>00 00 00 00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="DINT" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="SrcASCVal" DataType="DINT" Radix="Decimal" ExternalAccess="None">
<DefaultData>00 00 00 00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="DINT" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="TrimDone" DataType="BOOL" Radix="Decimal" ExternalAccess="None">
<DefaultData>00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="ScanCount" DataType="DINT" Radix="Decimal" ExternalAccess="None">
<DefaultData>00 00 00 00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="DINT" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="ScanNext" DataType="BOOL" Radix="Decimal" ExternalAccess="None">
<DefaultData>00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="WorkDest" DataType="DINT" Radix="Decimal" ExternalAccess="None">
<DefaultData>00 00 00 00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="DINT" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="SkipChar" DataType="BOOL" Radix="Decimal" ExternalAccess="None">
<DefaultData>00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="SkipUnderscore" DataType="BOOL" Radix="Decimal" ExternalAccess="None">
<DefaultData>00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="BOOL" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
<LocalTag Name="ScanValue" DataType="DINT" Radix="Decimal" ExternalAccess="None">
<DefaultData>00 00 00 00</DefaultData>
<DefaultData Format="Decorated">
<DataValue DataType="DINT" Radix="Decimal" Value="0"/>
</DefaultData>
</LocalTag>
</LocalTags>
<Routines>
<Routine Name="Logic" Type="RLL">
<RLLContent>
<Rung Number="0" Type="N">
<Text>
<![CDATA[OTU(DN)OTU(EM)OTU(ER)MOV(Source.LEN,SrcLength);]]>
</Text>
</Rung>
<Rung Number="1" Type="N">
<Comment>
<![CDATA[First check for an empty source string, and, if so, jump directly to the end with the Dest parameter unchanged, as does the native STOD instruction.]]>
</Comment>
<Text>
<![CDATA[EQU(SrcLength,0)[OTL(EM) ,JMP(lblEND) ];]]>
</Text>
</Rung>
<Rung Number="2" Type="N">
<Comment>
<![CDATA[Since there is at least one character in the string, set the result -- Dest -- to zero as per STOD.]]>
</Comment>
<Text>
<![CDATA[[CLR(Dest) ,CLR(WorkDest) ,CLR(SrcIndex) ];]]>
</Text>
</Rung>
<Rung Number="3" Type="N">
<Comment>
<![CDATA[Do...While:  Trim all leading non-numeric/HEX characters as per STOD, as well as leading zeros.]]>
</Comment>
<Text>
<![CDATA[LBL(lblTrim)NOP();]]>
</Text>
</Rung>
<Rung Number="4" Type="N">
<Text>
<![CDATA[MOV(Source.DATA[SrcIndex],SrcASCVal);]]>
</Text>
</Rung>
<Rung Number="5" Type="N">
<Comment>
<![CDATA[Skip characters until 1 to 9, or A to F, or a to f is encountered.]]>
</Comment>
<Text>
<![CDATA[[LIM(49,SrcASCVal,57) ,LIM(65,SrcASCVal,70) ,LIM(97,SrcASCVal,102) ]OTE(TrimDone);]]>
</Text>
</Rung>
<Rung Number="6" Type="N">
<Comment>
<![CDATA[Index to the next character in continue with Trim Do...While]]>
</Comment>
<Text>
<![CDATA[XIO(TrimDone)[ADD(1,SrcIndex,SrcIndex) ,LES(SrcIndex,SrcLength) JMP(lblTrim) ];]]>
</Text>
</Rung>
<Rung Number="7" Type="N">
<Comment>
<![CDATA[Jump to the END if there are no valid numeric/HEX characters in the string to convert.  Result will be zero, and successful, as per STOD.]]>
</Comment>
<Text>
<![CDATA[GEQ(SrcIndex,SrcLength)[OTL(DN) ,JMP(lblEND) ];]]>
</Text>
</Rung>
<Rung Number="8" Type="N">
<Comment>
<![CDATA[Reaching here, SrcIndex will be pointing to the first (MSD) character in the string to convert.  Initialize counters for scannig.  By default do not skip underscores unless 16# is prefixed.]]>
</Comment>
<Text>
<![CDATA[CLR(WorkDest)CLR(ScanCount)OTU(SkipUnderscore);]]>
</Text>
</Rung>
<Rung Number="9" Type="N">
<Comment>
<![CDATA[Do...While:  Scan through the string until the first non-numeric/HEX character, or end of the string.  Move valid HEX digit values into a DINT array.]]>
</Comment>
<Text>
<![CDATA[LBL(lblScan)CLR(ScanValue)OTU(SkipChar)OTU(ScanNext);]]>
</Text>
</Rung>
<Rung Number="10" Type="N">
<Comment>
<![CDATA[ASCII zero]]>
</Comment>
<Text>
<![CDATA[EQU(SrcASCVal,48)OTL(ScanNext);]]>
</Text>
</Rung>
<Rung Number="11" Type="N">
<Comment>
<![CDATA[ASCII 1 to 9]]>
</Comment>
<Text>
<![CDATA[XIO(ScanNext)LIM(49,SrcASCVal,57)SUB(SrcASCVal,48,ScanValue)OTL(ScanNext);]]>
</Text>
</Rung>
<Rung Number="12" Type="N">
<Comment>
<![CDATA[ASCII A to F]]>
</Comment>
<Text>
<![CDATA[XIO(ScanNext)LIM(65,SrcASCVal,70)SUB(SrcASCVal,55,ScanValue)OTL(ScanNext);]]>
</Text>
</Rung>
<Rung Number="13" Type="N">
<Comment>
<![CDATA[ASCII a to f]]>
</Comment>
<Text>
<![CDATA[XIO(ScanNext)LIM(97,SrcASCVal,102)SUB(SrcASCVal,87,ScanValue)OTL(ScanNext);]]>
</Text>
</Rung>
<Rung Number="14" Type="N">
<Comment>
<![CDATA[Special Case:  Ignore ASCII underscores embeddied in the string, but only if "16#" was used as a prefix.]]>
</Comment>
<Text>
<![CDATA[XIO(ScanNext)XIC(SkipUnderscore)EQU(SrcASCVal,95)OTL(SkipChar)OTL(ScanNext);]]>
</Text>
</Rung>
<Rung Number="15" Type="N">
<Comment>
<![CDATA[Special Case:  Ignore the prefix consisting of "16#" commonly used when writing HEX strings.]]>
</Comment>
<Text>
<![CDATA[XIO(ScanNext)EQU(SrcASCVal,35)EQU(ScanCount,2)EQU(WorkDest,16#16)[CLR(WorkDest) ,CLR(ScanCount) ,OTL(SkipUnderscore) ,OTL(SkipChar) OTL(ScanNext) ];]]>
</Text>
</Rung>
<Rung Number="16" Type="N">
<Comment>
<![CDATA[If not skipping this character, shift the working result and add the next digit.  Then save the digit for later inspection.]]>
</Comment>
<Text>
<![CDATA[XIC(ScanNext)XIO(SkipChar)[BTD(WorkDest,0,WorkDest,4,28) AND(WorkDest,16#FFFFFFF0,WorkDest) OR(WorkDest,ScanValue,WorkDest) ,ADD(1,ScanCount,ScanCount) ];]]>
</Text>
</Rung>
<Rung Number="17" Type="N">
<Comment>
<![CDATA[Increment the indexes and verify bounds to continue with loop.]]>
</Comment>
<Text>
<![CDATA[XIC(ScanNext)ADD(1,SrcIndex,SrcIndex)[GEQ(SrcIndex,SrcLength) ,GRT(ScanCount,8) OTL(ER) ]OTU(ScanNext);]]>
</Text>
</Rung>
<Rung Number="18" Type="N">
<Comment>
<![CDATA[Get the next character from the string and continue with Scan Do...While.]]>
</Comment>
<Text>
<![CDATA[XIC(ScanNext)[MOV(Source.DATA[SrcIndex],SrcASCVal) ,JMP(lblScan) ];]]>
</Text>
</Rung>
<Rung Number="19" Type="N">
<Comment>
<![CDATA[Reaching here, all of the HEX values have been combined into the woking destination; now move to the return parmeter.]]>
</Comment>
<Text>
<![CDATA[[MOV(WorkDest,Dest) ,XIC(S:V) OTL(ER) ];]]>
</Text>
</Rung>
<Rung Number="20" Type="N">
<Text>
<![CDATA[LBL(lblEND)NOP();]]>
</Text>
</Rung>
<Rung Number="21" Type="N">
<Text>
<![CDATA[XIO(EM)XIO(ER)OTL(DN);]]>
</Text>
</Rung>
</RLLContent>
</Routine>
</Routines>
<Dependencies>
<Dependency Type="DataType" Name="STRING10"/>
</Dependencies>
</AddOnInstructionDefinition>
</AddOnInstructionDefinitions>
</Controller>
</RSLogix5000Content>